Emergency Lighting Products
Eaton 93PM Emergency Lighting (20-120 kW)
10–400 kW
Product Overview
Appropriate and effective emergency lighting systems are vital to facilitate occupant egress during an emergency, such as a building fire or other dangerous situation. In addition to prioritizing safety, proper emergency lighting is required by building codes such as NFPA 101, the Life Safety Code. Trust Eaton’s emergency lighting UPSs (10-200 kVA) to keep your occupants safe and your commercial structures up to code. Our emergency lighting UPSs (10-200 kVA) are UL 924 tested and certified, providing the industry’s highest capacity and smallest footprint options for emergency lighting applications.
Features & Benefits
- UL 924 tested and certified to meet NFPA 101 (Life Safety Code) and other important building codes
- An Eaton factory limited warranty, technical support and options for service and monitoring/management plans (PredictPulse) provide investment protection and peace-of-mind
- Portfolio includes solutions that boast industry-leading efficiency with Eaton’s Energy Saver System (ESS) and small footprints
- Standard accessories available with UL 924 systems including communications cards, maintenance bypasses and distribution cabinets
Eaton 93PM Emergency Lighting
UPS Rating (1.0 power factor) | ||||
kW | 20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 120 | |||
General Characteristics | ||||
Audible noise | 65 dBA at 120 kW | |||
Altitude (max) | 1,500 meters / 4,922 feet | |||
Scalability | Up to 3 internal power modules External parallel with up to 8 UPSs Interact with the 93PM to take a closer look |
|||
Efficiency | 93PM efficiency with ESS- 99% 93PM double-conversion efficiency- up to 97% |
|||
Input Characteristics | ||||
Voltage | 480V | |||
Voltage range | +10% / -10% | |||
Frequency range | 50/60 Hz | |||
Power factor | ≥ .99 | |||
Input current distortion | <3% @ 100% load capacity | |||
Soft start capability | Yes | |||
Internal backfeed protection | Yes | |||
Output Characteristics | ||||
Voltage | 480V | |||
Regulation | ±1% steady state | |||
Inverter | PWM with IGBT Switching | |||
Voltage THD | < 1% (100% linear load); < 5% (non-linear load) |
|||
Load power factor range | .8 leading to .8 lagging without de-rating | |||
Heat dissipation (BTU/Hr x 1000/Hr) | 20 kW, 480V: 2.55 30 kW, 480V: 3.58 40 kW, 480V: 4.56 50 kW, 480V: 5.70 60 kW, 480V: 7.16 70 kW, 480V: 8.36 | 80 kW, 480V: 9.12 90 kW, 480V: 10.26 100 kW, 480V: 11.40 110 kW, 480V: 12.54 120 kW, 480V: 13.68 |
||
Battery | ||||
Battery type | VRLA | |||
Battery voltage | 480V | |||
Charging method | ABM or float technology | |||
Dimensions and Weights | ||||
Height (mm/inches) | Width (mm/inches) | Depth (mm/inches) | ||
93PM Emergency Lighting UPS | 1880/74 | 559/22 | 1067/42 | |
Serviceability | ||||
Back/side against wall installation | Standard, front access only | |||
Certification | ||||
Safety | UL 924 Emergency Lighting and Power | |||
EMC | FCC Part 15 Subpart B Class A | |||
Surge | IEC 61000-4-5 | |||
Optional line and match accessories | ||||
External slim maintenance bypass | ||||
eNotify Remote Monitoring service option | ||||
24x7 remote monitoring of UPS and battery alarms, daily heartbeat check and monthly report. eNotify requires the PXGX-UPS Card and Environmental Monitoring Probe | ||||
Communication Options | ||||
The following connectivity options can be installed at any time: | Power Xpert Gateway Mini-slot communication card Industrial relay card |