Emergency Lighting Products
Eaton 9355 Emergency Lighting
10–30 kVA

Product Overview
Appropriate and effective emergency lighting systems are vital to facilitate occupant egress during an emergency, such as a building fire or other dangerous situation. In addition to prioritizing safety, proper emergency lighting is required by building codes such as NFPA 101, the Life Safety Code. Trust Eaton’s emergency lighting UPSs (10-200 kVA) to keep your occupants safe and your commercial structures up to code. Our emergency lighting UPSs (10-200 kVA) are UL 924 tested and certified, providing the industry’s highest capacity and smallest footprint options for emergency lighting applications.
Features & Benefits
- UL 924 tested and certified to meet NFPA 101 (Life Safety Code) and other important building codes
- An Eaton factory limited warranty, technical support and options for service and monitoring/management plans (PredictPulse) provide investment protection and peace-of-mind
- Portfolio includes solutions that boast industry-leading efficiency with Eaton’s Energy Saver System (ESS) and small footprints
- Standard accessories available with UL 924 systems including communications cards, maintenance bypasses and distribution cabinets
Eaton 9355 Emergency Lighting Technical Specifications
Information | |
UL 924 Market | Emergency |
Configuration | Tower |
Electrical Information | |
Electrical Connections | Hardwired. See manual for terminal block layout. |
Operating Frequency | 50/60 Hz |
Input Power Factor | > 0.99 typical |
Input Current Distortion | 5% THD |
Output Voltage Regulation | ±1% Static; ±5% dynamic at 100% resistive load change, <1 ms response time |
Overload Capacity | 150% for 5 sec / 125% for 1 min (online), 110% for 10 min (Normal Operation) |
Communications | |
Communication Ports | (1) RS-232, (1) Relay Contact, (1) REPO, (2) Environmental Input |
Communication Slot | (2) X-Slot communication bays, where system provided with (1) gateway card factory installed |
Environmental & Standards | |
Audible Noise | <53 dBA @ 1 meter, typical |
Operating Temperature | 10°C to + 40°C, +45°C with 7.5% derating; Batteries recommended max. +25°C |
Safety Markings | IEC62040-1:2008/A1:2013, UL 1778, UL 924 |
Markings | UL, cULus |
Quality and Environment | ISO 9001:2008 and ISO 14001:2004 |
Storage Temperature | -15°C to +25°C |
Relative Humidity | 0-95%, non-condensing |
Altitude | <1000m at +40°C, <3000m at +25°C |
Eaton 9355 Emergency Lighting UPS Models
System Rating | Unit Description | Part Number | Qty | Voltage | System Dimensions (H x W x D, inches) | System Weight (lb) |
---|---|---|---|---|---|---|
8.5 kVA/kW | UPS EBM | BH10KEL2083P100 BHEBM96EL600 | 1 2 | 208V three phase | 47.8 x 36 x 33.7 | 2029 |
13.1 kVA/kW | UPS EBM | BH15KEL2083P100 BHEBM96EL600 | 1 3 | 208V three phase | 47.8 x 48 x 33.7 | 2739 |
18 kVA/kW | UPS EBM | BH20KEL2083P100 BHEBC72EL600 | 1 2 | 208V three phase | 66 x 60 x 34.1 | 5280 |
24 kVA/kW | UPS EBM | BH30KEL208SF100 BHEBC72EL600 | 1 2 | 208V three phase | 66 x 60 x 34.1 | 5280 |
27 kVA/kW | UPS EBM | BH30KEL2083P100 BHEBC72EL600 | 1 3 | 208V three phase | 66 x 80 x 34.1 | 7340 |
18 kVA/kW | UPS EBM XFMR | BH20KEL2083P100 BHEBC72EL600 BHKBT004200 | 1 2 1 | 480V three phase | 66 x 80 x 34.1 | 6072 |
24 kVA/kW | UPS EBM XFMR | BH30KEL208SF100 BHEBC72EL600 BHKBT004200 | 1 2 1 | 480V three phase | 66 x 80 x 34.1 | 6072 |
24 kVA/kW | UPS EBM XFMR | BH30KEL208SF100 BHEBC72EL600 BHKBT004200 | 1 3 1 | 480V three phase | 66 x 100 x 34.1 | 8132 |