Product Overview

Appropriate and effective emergency lighting systems are vital to facilitate occupant egress during an emergency, such as a building fire or other dangerous situation. In addition to prioritizing safety, proper emergency lighting is required by building codes such as NFPA 101, the Life Safety Code. Trust Eaton’s emergency lighting UPSs (10-200 kVA) to keep your occupants safe and your commercial structures up to code. Our emergency lighting UPSs (10-200 kVA) are UL 924 tested and certified, providing the industry’s highest capacity and smallest footprint options for emergency lighting applications.

Features & Benefits

  • UL 924 tested and certified to meet NFPA 101 (Life Safety Code) and other important building codes
  • An Eaton factory limited warranty, technical support and options for service and monitoring/management plans (PredictPulse) provide investment protection and peace-of-mind
  • Portfolio includes solutions that boast industry-leading efficiency with Eaton’s Energy Saver System (ESS) and small footprints
  • Standard accessories available with UL 924 systems including communications cards, maintenance bypasses and distribution cabinets

93PM Auxiliary Lighting Technical Specifications

UPS Rating (1.0 power factor)
kW20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 120, 130, 140, 150, 160, 170, 180, 190, 200
General Characteristics
Audible noise65 dBA at 200 kW
Altitude (max)1,500 meters / 4,922 feet
ScalabilityUp to 4 internal power modules
External parallel with up to 8 UPSs Interact with the 93PM to take a closer look
Efficiency93PM efficiency with ESS- 99%
93PM double-conversion efficiency- up to 97%
Input Characteristics
Voltage480 (208 with IAC-D)
Voltage range+10% / -10%
Frequency range50/60 Hz
Power factor≥ .99
Input current distortion<3% @ 100% load capacity
Soft start capabilityYes
Internal backfeed protectionYes
Output Characteristics
Voltage480 (208 with IAC-D)
Regulation±1% steady state
InverterPWM with IGBT Switching
Voltage THD< 1% (100% linear load);
< 5% (non-linear load)
Load power factor range.8 leading to .8 lagging without de-rating
Heat dissipation
(BTU/Hr x 1000/Hr)
20 kW, 480V: 2.55
30 kW, 480V: 3.58
40 kW, 480V: 4.56
50 kW, 480V: 5.70
60 kW, 480V: 7.16
70 kW, 480V: 8.36
80 kW, 480V: 9.12
90 kW, 480V: 10.26
100 kW, 480V: 11.40
110 kW, 480V: 12.54
120 kW, 480V: 13.68
130 kW, 480V: 14.82
140 kW, 480V: 15.96
150 kW, 480V: 17.10
160 kW, 480V: 18.24
170 kW, 480V: 19.38
180 kW, 480V: 20.52
190 kW, 480V: 21.66
200 kW, 480V: 22.80
Battery
Battery typeVRLA
Battery voltage480V
Charging methodABM or float technology
Dimensions and Weights
UPS ModelHeight (mm/inches)Width (mm/inches)Depth (mm/inches)
93PM Auxiliary Lighting UPS - 50, 100, 150 frame1880/74559/221067/42
93PM Auxiliary Lighting UPS- 200 frame1880/74813/321067/42
Serviceability
Back/side against wall installationStandard, front access only
Certification
SafetyUL 924 Auxiliary Lighting
EMCFCC Part 15 Subpart B Class A
SurgeIEC 61000-4-5
Optional line and match accessories
  • External slim maintenance bypass
  • Integrated distribution cabinet (with input and output transformer options)
  • Integrated parallel tie cabinets
  • Integrated battery cabinet (small and large)

eNotify Remote Monitoring service option
24x7 remote monitoring of UPS and battery alarms, daily heartbeat check and monthly report. eNotify requires the PXGX-UPS Card and Environmental Monitoring Probe
Communication Options
The following connectivity options can be installed at any time:Power Xpert Gateway Mini-slot communication card
Industrial relay card
Due to continuing improvements, specifications are subject to change without notice.

93PM Auxiliary Lighting Document Downloads

Eaton 93PM UPS Brochure

  •  File Type: PDF
  •  File Size: 2.76 MB
Download Brochure