Serving Ohio's Critical Power needs for 30+ years
The energy-efficient Eaton 9390 UPS provides backup power and scalable battery runtimes in a small footprint for mid-size data centers, medical equipment and other critical systems. With the groundbreaking Energy Saver System, the 9390 operates at 99% UPS efficiency and can pay for itself in three to five years—without sacrificing reliability.
| Power Rating | 20-160 kVA |
| Voltage | 208/208, 380/380, 400/400, 480/480 (standard) 600/600, 600/208, 480/208 (optional) |
| Frequency | 55-65 Hz |
| Configuration | Tower |
| Product Series | Powerware |
| UPS Rating (0.9 power factor) | |
| kVA | 20, 40, 80, 120, 160 |
| kW | 18, 36, 72, 108, 144 |
| General Characteristics | |
| Efficiency | 99% with Energy Saver Mode |
| Parallel Capability | Four modules with tie cabinet |
| Audible Noise | <65 dBA @ 1 meter |
| Altitude (max) | 2000m at 104°F (40°C) |
| Input Characteristics | |
| Voltage | 208, 380, 400, 415, 480, 6001 |
| Voltage Range | +10% / -15%2 |
| Frequency range | 55-65 Hz |
| Power Factor | 0.99 (min) |
| Input Current Distortion | <4.5% |
| Soft Start Capability | Yes |
| Internal Backfeed Protection | Yes |
| Broadcast global support | Yes |
| Output Characteristics | |
| Voltage | 2083, 3803, 4003, 4153, 4803 , 6004 |
| Regulation | ±1% |
| Inverter | PWM with IGBT Switching |
| Voltage THD | < 2% (100% linear load); < 5% (non-linear load) |
| Load Power Factor Range | Down to 0.9pf leading without de-rating |
| Heat dissipation (BTU/Hr x 1000/Hr) |
80 kVA, 208V: 23.6 160 kVA, 208V: 47.3 80 kVA, 380-480V: 21.9 160 kVA, 380-480V: 43.8 |
| Battery | |
| Battery types | VRLA, AGM, Gel, Wet, Eaton batteries also available |
| Battery voltage | 384 – 480 V |
| Temperature Compensation | Optional |
| Charging method | Advanced battery management |
| Dimensions and Weights | |
| 40-80 kVA modules | HxWxD: 73.7 x 18.9 x 31.6 in./1872 x 480 x 803 mm |
| 40-80 kVA Modules | 640 lb./290 kg (208V); 568 lb./258 kg (480V) |
| 120-160 kVA Modules | HxWxD: 73.7 x 35.6 x 31.6 in./1872 x 904 x 803 mm |
| 120-160 kVA Modules | 1,060 lb./481 kg (208V, 480V) |
| Serviceability | |
| Back/Side Against Wall Installation | Standard |
| Certification | |
| Safety | UL1778, cUL |
| EMC | IEC62040-2 EN50091 Class A (restricted access) |
| Surge | ANSI C62, 41 Cat. A&B |
| Accessories | |
| Module tie cabinet | Optional |
| External Maintenance Bypass | Optional |
| Integrated Distribution Cabinet | Optional |
| Isolation Transformer | Optional |
| eNotify Remote Monitoring service option | |
| 24×7 remote monitoring of UPS and battery alarms, daily heartbeat check and monthly report. eNotify requires the PXGX-UPS Card and Environmental Monitoring Probe | |
| Communication Options | |
| Software Compatibility | Intelligent Power Manager, PowerVision, LanSafe, FORESEER, Power Xpert |
| Communication Cards | Standard system includes one ConnectUPS Web/ SNMP/-X Card with an Environment Monitoring Probe. Two communications bays standard. Four communication bays included. The following connectivity card options can be installed at any time:
|
| Remote Inputs/Outputs | Two building alarms inputs and one summary alarm contact (5A@120V) standard |
| Four more building alarm inputs available with the Communications Expansion | |
| Option Remote panel | Eight backlit status indicator lamps plus an audible horn |
Due to continuing improvements, specifications are subject to change without notice.